Decorative round surface-mounted luminaire. For escape route illumination. Base: metal, powder-coated. Diffuser made of plastic (polycarbonate), opal, shockproof. Diffuser fastening: patented push system. Suitable for Ceiling mounting, Wall (surface). Self-contained system with automatic self-test and feedback to the RZB monitoring system MULTIDIGIT.
Technical Specifications
Typ of emergency lighting | Self-contained system |
---|---|
Monitoring | MultiDigit |
Battery | NiMh |
Duration | 3 h |
Operating mode | Non-maintained power mode and maintained power mode |
Diameter D | 620 mm |
Height H | 160 mm |
Weight | 4.28 kg |
Light source | LED |
Colour temperature | 4000 K |
Rated luminous flux, mains operation | 4400 lm |
System power, mains operation | 37 W |
Rated luminous flux, emergency operation | 430 lm |
System efficiency | 119 lm/W |
Glare evaluation RUG (4H 8H) | 19,8 |
Beam angle |
down 113° up 180° |
Colour rendering index (CRI) | 80 |
Colour tolerance (McAdam) | 4 SDCM |
Photobiological safety according to EN 62471 | Risk group 0 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 50 - 60 Hz |
Luminaires on B10A fuse | 15 |
Luminaires on B16A fuse | 25 |
Luminaires on C10A fuse | 26 |
Luminaires on C16A fuse | 42 |
Inrush current / Inrush current duration | 10 A / 50 µs |
CIE Flux Code / CEN Flux Code | 43 73 91 92 100 |
Type of protection | IP 40 |
Protection class | I |
Filament test | 850°C - 30 seconds |
Impact resistance | IK10 |
Ambient temperature for maintained power | 5 °C ... + 25 °C |
Ambient temperature for non-maintained power mode | 5 °C ... + 40 °C |
Conformity mark | CE , EAC |
Downloads
Light Calculator
The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.