Attractive cylindrical bollard with innovative housing design and high-quality LED optics. For escape route illumination. Luminaire tube Ø 115 mm made of corrosion-resistant aluminium profile, powder coated. Recessed stainless steel fixing plate. Non-corrosive gear compartment made of mould-cast dual compound thermoplastic with integral TP gasket. With membrane valve to avoid condensation. Luminaire head made of corrosion-resistant pressure die-cast aluminium, powder-coated, with transparent cylinder (glass) and translucent anti-glare louvres. Connection box on base, max. 2 x 3 x 2.5 mm² for through wiring.Driver integrated. Suitable for connection to central battery systems. With AC Control monitoring module for LUXIFAIR central battery units.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Luxifair AC-Control |
Battery | without |
Operating mode | maintained power mode |
Diameter D | 115 mm |
Height H | 1000 mm |
Weight | 5.45 kg |
Light source | LED |
Colour temperature | 3000 K |
Rated luminous flux, mains operation | 880 lm |
System power, mains operation | 11 W |
Rated luminous flux, emergency operation | 880 lm |
System power, emergency operation | 11 W |
System efficiency | 80 lm/W |
Glare evaluation RUG (4H 8H) | 24,9 |
Beam angle |
down 90°/90°/90°/90° up 90°/90°/90°/90° |
Colour rendering index (CRI) | 80 |
Photobiological safety according to EN 62471 | Risk group 1 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 Hz, 60 Hz |
Luminaires on B10A fuse | 39 |
Luminaires on B16A fuse | 63 |
Luminaires on C10A fuse | 63 |
Luminaires on C16A fuse | 100 |
Inrush current / Inrush current duration | 8 A / 5 µs |
CIE Flux Code / CEN Flux Code | 8 34 71 62 100 |
Type of protection | IP 65 |
Protection class | I |
Filament test | 650 °C |
Impact resistance | IK05 |
Ambient temperature for maintained power | -10 °C ... + 35 °C |
Conformity mark | CE |