Flexible square recessed multifunction downlight. Luminaire for escape route illumination. Housing: sheet steel, powder-coated. Luminaire frame: aluminium, powder-coated. Diffuser made of non-yellowing plastic (PMMA), opal. LED backlight technology for homogeneous illumination of the entire light-emitting surface. Ceiling installation with spring system. Including separate LED converter with connecting cable 250 mm. Zum Anschluss an zentrale Sicherheitsstromversorgung geeignet. Mit Überwachungsbaustein AC-Control für LUXIFAIR Zentralbatterie-Anlagen.

Technical Specifications

Typ of emergency lighting Central battery system
Monitoring Luxifair AC-Control
Battery without
Operating mode maintained power mode
Length L 310 mm
Width B 310 mm
Height H 2 mm
Cut-out length LA 297 mm
Cut-out width BA 297 mm
Installation space height HE 60 mm
Luminaire: recess height HEL 42 mm
Ceiling thickness S 1-20 mm
Weight 1.17 kg
Light source LED
Colour temperature 3000 K | 4000 K
Rated luminous flux, mains operation 2150 lm
System power, mains operation 17 W
Rated luminous flux, emergency operation 860 lm
System power, emergency operation 7,4 W
System efficiency 126 lm/W
Glare evaluation RUG (4H 8H) 24,6
Beam angle 112°
Rated life 50000 h
Colour rendering index (CRI) 80
Photobiological safety according to EN 62471 Risk group 1
Driver Converter
Control on/off
Voltage 220 - 240 V / 0 Hz, 50 Hz, 60 Hz
Luminaires on B10A fuse 31
Luminaires on B16A fuse 50
Luminaires on C10A fuse 52
Luminaires on C16A fuse 85
Inrush current / Inrush current duration 5 A / 50 µs
CIE Flux Code / CEN Flux Code 47 79 96 100 100
Type of protection IP 54 on room side
IP 20
Protection class II
Filament test 650 °C
Impact resistance IK03
Ambient temperature for maintained power -10 °C ... + 35 °C
Ambient temperature for non-maintained power mode -10 °C ... + 35 °C
Safety marks Do not cover the recessed luminaire!
Conformity mark CE , EAC