Wishlist

TOLEDO FLAT+ round

901812.0031

Recessed downlights, anthracite metallic (DB703)

Flexible round recessed multifunction downlight. Housing made of sheet steel, powder-coated. Luminaire frame: aluminium, powder-coated. Light guide and diffuser made of non-yellowing PMMA, opal matt. LED backlight technology for homogeneous illumination of the entire light-emitting surface. MultiColour: Colour temperature individually adjustable either 3000 K or 4000 K via switching element. Factory setting is 4000 K. MultiLumen: 4 steps adjustable luminous flux. Factory setting is step 2. Suitable for Recessed ceiling mounting. Ceiling installation with spring system. Can be directly covered with thermal insulation material (applies only to the lower lumen levels). Including separate LED converter with connecting cable 250 mm. Suitable for through-wiring with separately available accessories. Through-wiring box (5 pole) available as accessory. Surface mounted housing as accessory for all sizes.

Technical Specifications

Diameter D 470 mm
Height H 2 mm
Cut-out diameter DA 457 mm
Luminaire: recess height HEL 41 mm
Ceiling thickness S 1-20 mm
Installation space length LE 630 mm
Installation space width BE 570 mm
Installation space height HE 70 mm
Weight 1.57 kg
Light source LED
Colour temperature 3000 K | 4000 K
Rated luminous flux 3050 lm | 3550 lm | 4000 lm | 4450 lm
System power 22 W | 26 W | 30 W | 33 W
System efficiency 133 lm/W | 135 lm/W | 137 lm/W | 139 lm/W
Glare evaluation RUG (4H 8H) 23,3 | 23,9 | 24,3 | 24,6
Beam angle 113°
Rated life 50000 h (L80/B10)
Colour rendering index (CRI) 80
Colour tolerance (McAdam) 3 SDCM
Photobiological safety according to EN 62471 Risk group 1
Driver Converter
Control on/off
Voltage 220 - 240 V / 50 Hz, 60 Hz
Luminaires on B10A fuse 21
Luminaires on B16A fuse 33
Luminaires on C10A fuse 27
Luminaires on C16A fuse 44
Inrush current / Inrush current duration 27.3 A / 144 µs
CIE Flux Code / CEN Flux Code 47 79 96 100 100
Type of protection IP 54 on room side
IP 20
Protection class II
Filament test 650 °C
Impact resistance IK03
Ambient temperature -20 °C bis + 35 °C
Safety marks Do not cover the recessed luminaire!
Conformity mark CE , EAC

Light Calculator

Room
Reflection rate 70 / 50 / 20
Calculation
Maintenance factor 0,8
Result
lx Illumination value Em
Quantity of Luminaires
lx Illumination value Em
W Total power
lm Total luminous flux
Download PDF

The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.

Accessories

982920.0031
Surface mounted housing
982924.0031
Insert frames for modular grid ceilings 600.
982925.0031
Insert frames for modular grid ceilings 625.
982703.002
Through-wiring box
983080.0031
refurbishment frames for recessed luminaires
983110.002
HF movement sensor in separate box.