FLAT SLIM round
672653.002.1.F1
Decorative round surface-mounted luminaire for indoor and outdoor use. Base: pressure die-cast aluminium, powder-coated. Standard Gore™ Protective Vents diaphragm valve to avoid condensation. Diffuser made of plastic (polycarbonate), opal, shockproof. Diffuser fastening: bayonet system. Uniform lighting achieved by the use of LED panel boards. Suitable for Ceiling mounting, Wall (surface). Very easy installation thanks to plug & play connection. The large connection compartment on the back for convenient connections is also ideal for through wiring. Electronic ballast included. MULTIDIGIT AIR wireless monitoring system with automatic self-test and feedback via Bluetooth® via Android / iOS app. No bus line required. Easy configuration and commissioning as well as monitoring via app. Up to 100 self-contained emergency luminaires can be wirelessly networked and monitored. Maximum security thanks to push notification and gateway functionality. The app generates the log book quickly and automatically in PDF format, which can be archived locally or in the cloud.
Technical Specifications
Typ of emergency lighting | Self-contained system |
---|---|
Monitoring | MultiDigit air |
Battery | LiFePO4 |
Duration | 3 h |
Operating mode | maintained power mode |
Diameter D | 300 mm |
Height H | 70 mm |
Weight | 1.94 kg |
Light source | LED |
Colour temperature | 3000 K | 4000 K |
Rated luminous flux, mains operation |
3000 K: 1450 lm | 2400 lm 4000 K: 1450 lm | 2450 lm |
System power, mains operation |
3000 K: 14 W | 20 W 4000 K: 14 W | 20 W |
Rated luminous flux, emergency operation | 420 lm |
System efficiency |
3000 K: 104 lm/W | 120 lm/W 4000 K: 104 lm/W | 123 lm/W |
Glare evaluation RUG (4H 8H) |
3000 K: 22,6 | 24,4 4000 K: 22,6 | 24,4 |
Beam angle |
down 143° up 180° |
Rated life | 50000 h |
Colour rendering index (CRI) | 80 |
Photobiological safety according to EN 62471 | Risk group 1 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 50 Hz, 60 Hz |
Luminaires on B10A fuse | 31 |
Luminaires on B16A fuse | 50 |
Luminaires on C10A fuse | 52 |
Luminaires on C16A fuse | 85 |
Inrush current / Inrush current duration | 5 A / 50 µs |
CIE Flux Code / CEN Flux Code | 36 66 88 83 100 |
Type of protection | IP 65 |
Protection class | I |
Filament test | 850 °C |
Impact resistance | IK08 |
Ambient temperature for maintained power | 5 °C ... + 25 °C |
Ambient temperature for non-maintained power mode | 5 °C ... + 25 °C |
Safety marks | D-mark |
Conformity mark | CE , EAC |
Downloads
Light Calculator
The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.